7.
Re-light the appliance. With the control set to the maximum rate (large flame) position, place the Fire front &
fret in position and leave to heat up for 5 minutes. Check for satisfactory clearance of products by inserting a
lighted smoke match into the opening in the position shown in Fig 10, i.e. 100mm below the top, and 40mm
inside of the front face of the opening. All the smoke must be drawn into the flue. If spillage occurs, allow a
further 10 minutes. Should spillage still occur examine the chimney for the fault and rectify the cause. The test
should be repeated if an extractor fan is situated in the room, or in any connecting room, with all the doors in
that room opened.
Demonstrate the lighting and extinguishing procedures to the user.
$'9,6(7+$7
:
The curing effect of heating the coals will cause an initial odour, which although not harmful, may require
additional ventilation until the odour has disappeared.
Any debris or soot is cleaned from the appliance. Advise the customer that they should read their Users
Instructions before operating the fire and always follow the advice in the section headed Removal of Debris or
Soot Deposits
.
The appliance must be serviced annually by a competent person; i.e. a CORGI registered installer
in accordance with these instructions and that the appliance is checked for spillage in accordance with the method
detailed in these instructions.
The appliance is fitted with an Oxy-pilot to prevent the continued operation in the event of spillage occurring. If
the fire shuts OFF repeatedly the appliance must be turned off and not used until an expert is consulted.
Complete the section in the enclosed registration leaflet. Advise that any component or part of this appliance is
guaranteed against defective workmanship or faulty materials for a period of twelve months from the date of
purchase.
Any such part will be replaced free of charge on receipt of the purchasers address at the cost of postage only,
provided that:
a)
It is accompanied by the registration section cut out of the booklet together with the original purchase
receipt, which will be returned with the replacement part.
b)
A competent person has carried out installation repairs or adjustments, such as the suppliers representative
or a CORGI registered installer.
0$,17(1$1&($1'6(59,&,1*
GENERAL
A.
REMOVAL OF DEBRIS OR SOOT DEPOSITS;
Allow the appliance to cool for one hour before removing all the coals and coal bed components for cleaning
purposes. Once all the components have been removed from the fire bed check that no debris has become lodged
in the burner ports (both front and rear). If any debris is present it may be easily removed with a thin piece of card
or similar to ease out any foreign matter. To ensure that the release of fibres from these RCF articles is kept to a
minimum, during installation and servicing we recommend that you use a HEPA filtered vacuum to remove any
dust and soot accumulated in and around the fire before and after working on the fire. When replacing these
articles we recommend that the replaced items are not broken up, but are sealed within heavy-duty polythene
bags, clearly labelled as RCF waste. This is not classified as "hazardous waste" and may be disposed of at a
tipping site licensed for the disposal of industrial waste. Protective clothing is not required when handling these
articles, but we recommend you follow the normal hygiene rules of not smoking, eating or drinking in the work
area and always wash your hands before eating or drinking.
Any soot deposits may be removed from either the
Thermocouple or Electrode tips with a soft cloth, do not use abrasive materials.